HF-Performer 2 22-42 PL-T C L TL5C EII 220-240V
PHILIPS

HF-Performer 2 22-42 PL-T C L TL5C EII 220-240V

Regular price ₱1,200.00 ₱0.00 Unit price per

General Information

Application Code

EII

Type Version

mk4

Lamp Type

PL-T/C/L/TL5C

Number of Lamps

2 piece/unit

Number of Products on MCB (16A Type B) (Nom)

12

Automatic Restart

Yes

Operating and Electrical

Input Voltage

220 to 240 V

Input Frequency

50 to 60 Hz

Operating Frequency (Max)

- kHz

Operating Frequency (Min)

42 kHz

Operating Frequency (Nom)

45 kHz

Ignition Method

Warm Start

Crestfactor (Max)

1.7

Power Factor 100% Load (Nom)

0.95

Ignition Time (Max)

0.52 s

Mains Voltage Performance (AC)

-8%-+6%

Mains Voltage Safety (AC)

-10%-+10%

Earth Leakage Current (Nom)

0.5 mA

Inrush Current Width

0.35 ms

Constant Wattage Deviation

-2%/+2%

Ballast Factor (Nom)

1

Power Losses (Nom)

4.35-4.93 W

Inrush Current Peak (Max)

31 A

Wiring

Connector Type Input Terminals

Insert

Cable Capacity Output Wires Mutual (Nom)

100 pF

Connector Type Output Terminals

Insert

Cable Length Hot Wiring

0.75 m

Wire Striplength

7.5-8.5 mm

Dual Fixture Master/Slave

Not applicable  [ Master/Slave oper. not applicable]

Input Terminal Cross Section

0.50-1.50 mm²

Output Terminal Cross Section

0.50-1.50 mm²

Cable Capacity Output Wires to Earth (Nom)

100 pF

System characteristics

Rated Ballast-Lamp Power

22-42 W

Rated Lamp Power on PL-T/C

22/42 W

Temperature

T-Ambient (Max)

50 °C

T-Ambient (Min)

-25 °C

T-Storage (Max)

80 °C

T-Storage (Min)

-40 °C

T-Case Lifetime (Nom)

75 °C

T-Case Maximum (Max)

75 °C

T-Ignition (Max)

50 °C

T-Ignition (Min)

-25 °C

Emergency Operation

Battery Voltage Lamp Ignition

198-254 V

Battery Voltage Lamp Operation

176-254