HF-P 149 TL5 HO III 220-240V 5060Hz IDC
PHILIPS

HF-P 149 TL5 HO III 220-240V 5060Hz IDC

Regular price ₱700.00 ₱0.00 Unit price per

General Information

Application Code

III

Type Version

IDC

Lamp Type

TL5 HO

Number of Lamps

1 piece/unit

Number of Products on MCB (16A Type B) (Nom)

28

Automatic Restart

Yes

Operating and Electrical

Input Voltage

220 to 240 V

Input Frequency

50 to 60 Hz

Operating Frequency (Nom)

47.5 kHz

Ignition Method

Programmed Start

Crestfactor (Max)

1.7

Power Factor 100% Load (Nom)

0.99

Ignition Time (Max)

0.9 s

Mains Voltage Performance (AC)

-8%-+6%

Mains Voltage Safety (AC)

-10%-+10%

Earth Leakage Current (Nom)

0.5 mA

Inrush Current Width

0.25 ms

Constant Wattage Deviation

-2%/+2%

Ballast Factor (Nom)

1

Power Losses (Nom)

2.5 W

Inrush Current Peak (Max)

24 A

Wiring

Connector Type Input Terminals

WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]

Cable Capacity Output Wires Mutual (Nom)

200 pF

Connector Type Output Terminals

WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]

Cable Length Hot Wiring

0.75 m

Wire Striplength

8.0-9.0 mm

Dual Fixture Master/Slave

Not applicable  [ Master/Slave oper. not applicable]

Input Terminal Cross Section

0.50-1.00 mm²

Output Terminal Cross Section

0.50-1.00 mm²

Cable Capacity Output Wires to Earth (Nom)

200 pF

System characteristics

Rated Ballast-Lamp Power

49 W

Rated Lamp Power on TL5

49 W

System Power on TL5

57 W

Lamp Power on TL5

54.5 W

Power Loss on TL5

2.5 W

Rated Lamp Power on TL5 ECO

49 W

System Power on TL5 ECO

51 W

Lamp Power on TL5 ECO

48.5 W

Power Loss on TL5 ECO

2.5 W

Temperature

T-Ambient (Max)

60 °C

T-Ambient (Min)

-25 °C

T-Storage (Max)

80 °C

T-Storage (Min)

-40 °C

T-Case Lifetime (Nom)

80 °C

T-Case Maximum (Max)

80 °C

T-Ignition (Max)

60 °C

T-Ignition (Min)

-25 °C

Mechanical and Housing

Housing

L360x30x22

Emergency Operation

Nominal Light Output After 60 Seconds

100% of EBLF

Battery Voltage Lamp Ignition

198-254 V

Normal Operating Voltage (DC)

220-240 V

Battery Voltage Lamp Operation

176-254

Battery Voltage Guaranteed Operation

176-275 V

Battery Voltage Guaranteed Ignition

186-275 V

Emergency Ballast Lumen Factor (EBLF) (Nom)

100 %

Nominal Light Output After 5 Seconds

50% of EBLF